Based on your answers, Category 1 arc flash PPE is required for work.
You selected:
Panelboards or other equipment rated 240 volts and below.
Equipment Parameters:
Maximum of 25 kA available fault current; maximum of 0.03 sec (2 cycles) fault clearing time; minimum working distance 18 in.
Arc Flash Boundary:
19 inches
Category 1
4 cal/cm2 (16.75 J/cm2) (See Note A)
Required Arc-Rated Clothing:
Required Protective Equipment:
Image courtesy of Graphic Products.
Notes
AN: As needed (optional). AR: As required. SR: Selection required.
Note A: Arc rating is defined in Article 100 of NFPA 70E: Handbook for Electrical Safety in the Workplace (2018 edition).
Note B: Face shields are to have wrap-around guarding to protect not only the face but also the forehead, ears, and neck, or, alternatively, an arc-rated arc flash suit hood is required to be worn.
Note C: Other types of hearing protection are permitted to be used in lieu of or in addition to ear canal inserts provided they are worn under an arc-rated arc flash suit hood.
Note D: If rubber insulating gloves with leather protectors are used, additional leather or arc-rated gloves are not required. The combination of rubber insulating gloves with leather protectors satisfies the arc flash protection requirement.