Select the type of AC equipment:
Panelboards or other equipment rated 240 volts and belowPanelboards or other equipment rated greater than 240 volts and up to 600 volts600-volt class motor control centers (MCCs)Note: For equipment rated 600 volts and below and protected by upstream current-limiting fuses or current-limiting circuit breakers sized at 200 amperes or less, the arc flash PPE category can be reduced by one number but not below arc flash PPE category 1.
Informational Note to NFPA 70E Table 130.7(C)(15)(a): The following are typical fault clearing times of overcurrent protective devices:
Informational Note No. 1: See Table 1 of IEEE 1584TM, Guide for Performing Arc Flash Hazard Calculations, for further information regarding Notes b through d.
Informational Note No. 2: An example of a standard that provides information for arc-resistant switchgear referred to in Table 130.7(C)(15)(a) is IEEE C37.20.7, Guide for Testing Metal-Enclosed Switchgear Rated Up to 38 kV for Internal Arcing Faults.