Arc-resistant switchgear 1 kV through 15 kV

>

You selected:
Arc-resistant switchgear 1 kV through 15 kV [for clearing times of less than 0.5 sec (30 cycles) with an available fault current not to exceed the arc-resistant rating of the equipment], and metal-enclosed interrupter switchgear, fused or unfused of arc-resistant-type construction, 1 kV through 15 kV.

Equipment Parameters:
Maximum of 35 kA available fault current; maximum of up to 0.24  sec (15 cycles) fault clearing time; minimum working distance 36 in.